Fire safety requirements in the design and construction of buildings and structures are established in the technical regulations "General requirements for fire safety" (approved by the Order of the Ministry of Emergency Situations of 17.08.2021 No. 405, hereinafter referred to as the Technical Regulations).
According to paragraph 17 of the Technical Regulations, personal respiratory and visual protection equipment (self-rescuers) are provided to people in the premises of buildings of functional fire hazard subclasses F1.2, F1.5 and F4.3 located at a height of more than 28 m.
At the same time, in accordance with paragraph 18 of the Technical Regulations, individual and collective means of rescue are provided for buildings of functional fire hazard subclasses F1.2 and F1.5 with a height of more than 50 m.
It follows from the above that buildings not listed in paragraphs 17 and 18 of the Technical Regulations are not subject to the provision of personal respiratory and visual protection equipment (self-rescuers), as well as individual and collective means of rescue.